Energy
Power usage effectiveness (PUE) is the ratio of total data-centre energy to IT equipment energy (PUE = E_DC / E_IT). Lower is better; 1.0 would mean all energy goes to the IT load.
Power usage effectiveness (PUE) is the standard ratio for pue data center energy: total facility energy divided by the energy that reaches IT equipment (PUE = E_DC / E_IT). A value of 1.0 would mean every kilowatt-hour goes to servers, storage and network gear. Real sites sit above that because cooling, fans, UPS losses, lighting and auxiliaries take a share. Lower is better. The metric is simple enough for a board pack and precise enough that metering mistakes, boundary choices and annual averaging change the number more than operators expect.
Meter two boundaries. E_DC is the energy that enters the data centre (or the agreed facility boundary). E_IT is the energy delivered to IT equipment, usually taken at the UPS output or at PDU feeds that serve only IT load. PUE is E_DC / E_IT over the same period. Prefer an annual average over an instantaneous snapshot: a cold night with free cooling can flatter a site that runs hard in summer. Common mistakes: partial metering that misses CRACs or dry coolers; mixing office or warehouse load into E_DC; treating a UPS that also feeds non-IT plant as pure IT; ignoring backup generation where the reporting standard counts it; and comparing a design PUE to a measured annual PUE as if they were the same number.
A monthly board PUE collapses cooling towers, chillers, CRACs, UPS losses and lighting into one ratio. When the number moves, the chart does not say which plant moved it or for how many hours. Operators need the subsystems and the hours: which CRACs fought each other, which free-cooling window was missed, which chilled-water valve hunted overnight. PUE remains useful as a headline KPI. It is a poor triage tool on its own. Pair the ratio with metered cooling and power behaviour, or the number stays a score without a cause.
German law (Energieeffizienzgesetz, EnEfG § 11) sets hard PUE (Energieverbrauchseffektivität) limits for Rechenzentren. Sites that started operation before 1 July 2026 must hold an annual-average PUE ≤ 1.5 from 1 July 2027, and ≤ 1.3 from 1 July 2030, permanently. Sites that start from 1 July 2026 must reach PUE ≤ 1.2, and meet energy reuse (ERF per DIN EN 50600-4-6) of ≥ 10% (starts from July 2026), ≥ 15% (from July 2027) or ≥ 20% (from July 2028). Those Abs. 2 requirements apply as annual averages at latest two years after commissioning. Electricity used solely to upgrade waste heat for reuse is excluded from the PUE calculation under Abs. 2. Renewable electricity (Abs. 5): 50% from 1 January 2024, 100% from 1 January 2027 (bilanzziell). EnEfG binds operators in Germany; it is not a global PUE standard.
Under the EED data-centre scheme, operators of data centres with installed IT power demand ≥ 500 kW report KPIs to the European database (or a national scheme where the Member State runs one). The first deadline was 15 September 2024 for calendar year 2023; thereafter reports are due by 15 May each year for the preceding calendar year. PUE is calculated as E_DC / E_IT from the submitted figures; the Commission derives the indicator from that data. Related KPIs such as WUE, ERF and REF may appear in the same reporting set. Treat them as siblings of PUE, not substitutes for knowing where cooling waste sits hour by hour.
Explore is not a DCIM and it has no dedicated PUE product score. With facility and IT-load meters connected, and with the cooling points your BMS already exposes, the ratio and the cooling behaviour behind it become visible; cooling faults are where anomalies show. Findings land in one ranked queue priced by cost. That path is data center energy management in Explore: cooling-chain waste and PUE drift read from existing meters and BMS points, not a rack inventory tool. For the wider EMS definition see energy management system; many estates also expose plant over oBIX.
Before you ask
PUE is total data-centre energy divided by IT equipment energy (PUE = E_DC / E_IT). Lower is better. A perfect 1.0 would mean every kilowatt-hour goes to IT load; real sites sit above that because of cooling, UPS losses and auxiliaries.
Meter E_DC at the facility boundary and E_IT at UPS output or IT-only PDU feeds over the same period, then divide. Prefer an annual average. Avoid mixing non-IT building load into E_DC and avoid treating a shared UPS as pure IT.
It hides which cooling plant moved the ratio and for how many hours. Operators need subsystem meters and time series. Use PUE as a headline KPI, then triage with cooling and power behaviour behind it.
Sites started before 1 July 2026: annual-average PUE ≤ 1.5 from 1 July 2027 and ≤ 1.3 from 1 July 2030. Sites starting from 1 July 2026: PUE ≤ 1.2, plus rising ERF reuse floors, met as annual averages within two years of commissioning. Abs. 5 renewable shares are 50% from 2024 and 100% from 2027.
Operators of data centres with installed IT power demand ≥ 500 kW report KPIs to the European database (or a national scheme). After the first 15 September 2024 deadline for CY2023, filings are due by 15 May each year for the prior calendar year. PUE is E_DC / E_IT from the submitted data.
Explore has no dedicated PUE feature and is not a DCIM. With facility and IT-load meters connected it makes the ratio and the cooling behaviour behind it visible, and ranks cooling waste by cost. See data center energy management.