Degree days are a cumulative measure of how far outdoor temperature sits from a chosen base: heating degree days (HDD) below the base, cooling degree days (CDD) above it. Operators use them to weather-normalise building energy so year-on-year kWh comparisons are not just "it was a cold winter."
Degree days turn outdoor temperature into a weather workload for heating and cooling. A heating degree day (HDD) accumulates how far the daily mean sits below a base temperature. A cooling degree day (CDD) accumulates how far it sits above a (usually higher) cooling base. Add those °C·days over a week, month or season and you get a simple signal of weather-driven load. The number is not a thermostat setting and it is not a comfort score. It is a proxy for how hard the envelope and plant had to fight the outdoors.
The base temperature is a modelling choice about when the building starts needing heat or cool, given insulation, internal gains and plant behaviour. It is not the occupied setpoint on the wall. Regional practice differs, and one number does not fit every building. In the UK, Met Office and CIBSE-facing work often uses about 15.5°C for heating degree days, with a higher cooling base (around 22°C is common when cooling is analysed). CIBSE TM41 is the theory reference for degree-day methods; keep the detail in the guide, not in a marketing page. German practice is heating-led: the familiar 20/15 convention (VDI 3807 and related guidance) uses an indoor reference near 20°C and a heating threshold near 15°C, so a heating day is counted when the daily mean falls below 15°C. Swedish estates talk about graddagar and normalårskorrigering in energideklaration and district-heat follow-up; SMHI Energi-Index is often preferred over raw graddagar when the job is a full weather correction.
| Signal | What it measures | Typical use |
|---|---|---|
| Heating degree days (HDD) | Coldness below a heating base (°C·days) | Weather-correct space heating and heat networks |
| Cooling degree days (CDD) | Warmth above a cooling base (°C·days) | Weather-correct chillers and cooling plant |
| Simple ratio normalisation | Scale weather-dependent kWh by current/normal degree days | Quick year-on-year or season comparisons |
| Regression normalisation | kWh ≈ a + b·HDD + c·CDD (+ weekend/occupancy) | Baselines, exception bands, savings measurement |
A cold year burns more heat. A mild year looks like a saving even when nothing in the plant changed. Weather normalisation (also called weather-normalized energy) adjusts consumption so you can compare periods on a fair weather footing. The simple ratio method scales weather-dependent use by current degree days over normal (or baseline) degree days. A regression form is clearer when you have enough history: kWh ≈ a + b·HDD + c·CDD, often with a weekend or occupancy flag. The intercept a is the weather-independent base load; b and c are the weather slopes. Limitations matter. Better insulation and higher internal gains weaken how much degree days explain. Cooling-dominated sites, solar gains and humidity need more than HDD alone. If the model only ever saw heating season, do not trust it on a hot August.
Mismatch the base temperature between your HDD series and the one baked into a published "normal" and the ratio is noise. Skip the base-load split and you weather-correct lights and plugs that barely care about outdoor temperature. Use a remote weather station when the site sits in a different microclimate and the residuals look like plant faults. Incomplete meter periods, estimated gaps and mixed calendar months break both ratio and regression. Applying an HDD-only correction to a cooling-dominated load is the classic trap: the weather signal is pointing the wrong way.
Degree days are the weather covariate. They do not own the operating method. Energy monitoring and targeting (M&T), CUSUM charts and degree-day regression as a weekly exception process live in our Field Note on energy monitoring and targeting. This glossary stops at defining HDD, CDD and weather normalisation so that method page can stay the home for the workflow.
How FrostLogic Explore uses them. Explore's Energy Savings Loop measures approved changes at 7, 14 and 28 days against a weather-normalised baseline of the form kWh = a + b·HDD + c·CDD + d·weekend. There is no estimated-savings tier: money shows only when the customer set a tariff. Forecasts can use the same weather covariates. The commercial path for continuous meter reads is energy monitoring in Explore; the buildings-shaped commercial page is energy management for commercial buildings.
Before you ask
Heating degree days (HDD) accumulate how far outdoor temperature sits below a heating base. Cooling degree days (CDD) accumulate how far it sits above a cooling base. HDD tracks cold-weather heating load; CDD tracks warm-weather cooling load. Most northern European commercial estates are HDD-heavy; cooling-led sites need CDD in the model.
The base is an assumption about when the building needs heat or cool, given fabric and gains. Change the base and you change the degree-day count even if the weather file is identical. Mismatch the base between your series and a published normal and weather normalisation becomes noise.
No. UK practice often centres on about 15.5°C HDD (with a higher CDD base when cooling is analysed), with CIBSE TM41 as the theory reference. German heating practice commonly follows a 20/15 pattern (Heizgradtage / Gradtagzahl). Swedish work talks about graddagar and normalårskorrigering, and often prefers SMHI Energi-Index over raw graddagar for full weather correction. Always state which series you used.
Raw kWh includes the weather. A mild winter can look like a saving when the plant did nothing useful. Weather-normalised energy adjusts for HDD and CDD (and sometimes occupancy) so you can see whether the building's relationship with weather actually changed.
They are the weather input to baselines and exception charts, including degree-day regression and CUSUM-style tracking. The operating method (M&T, targeting, weekly review) is covered in energy monitoring and targeting. This page defines the weather signal; that article owns the workflow.
Explore measures approved changes against a weather-normalised baseline of the form kWh = a + b·HDD + c·CDD + d·weekend. Savings in money appear only when a tariff is set. See energy monitoring in Explore.