Integrations
Variable air volume (VAV) is an HVAC zone-control strategy that raises and lowers delivered airflow to match thermal (or ventilation) load. The terminal device is a VAV box fed by a central air handling unit.
Variable air volume (VAV) means the zone gets more or less supply air as load changes, instead of a constant-volume blast with reheat doing all the work. In a commercial VAV system, a central air handling unit feeds duct static; each zone's VAV box meters that air to the space. The contrast with constant air volume (CAV) is simple: CAV holds airflow fixed and varies temperature; VAV varies airflow (and may still reheat at minimum flow).
Space temperature (sometimes CO₂ or occupancy) resets an airflow setpoint between the box minimum and maximum. The VAV controller then drives the damper so delivered airflow tracks that setpoint. Occupied, unoccupied and standby modes usually change the minimum, the temperature setpoints, or both. When the box is at minimum and the zone is still cold, a reheat coil (hot water or electric) picks up the rest of the load.
Most commercial boxes are pressure-independent: two cascaded loops. The temperature (or IAQ) loop writes an airflow setpoint in CFM or l/s. A faster flow loop reads inlet differential pressure or a flow sensor, applies the box K-factor, and moves the damper so measured airflow holds even when upstream duct static swings. Pressure-dependent boxes skip the flow loop and map damper position more directly to load; they drift when static changes and are rarer on modern BMS jobs.
| Approach | What changes with load | How it relates |
|---|---|---|
| Variable air volume (VAV) | Zone airflow (and reheat at minimum) | This page: zone terminals on a central AHU |
| Constant air volume (CAV) | Supply temperature / reheat; airflow stays fixed | Older or simpler zones; more reheat energy at part load |
| Pressure-independent VAV box | Flow loop holds CFM despite duct static swings | Industry standard on modern commercial jobs |
| Pressure-dependent VAV box | Damper position more directly; no dedicated flow loop | Sensitive to upstream static; less common now |
A typical VAV point list includes zone temperature, airflow setpoint, measured airflow, damper command and/or position, reheat command (valve or SCR), and occupancy or minimum-flow mode. Many controllers also expose box discharge temperature and a local override or occupancy sensor. Those points live on the BMS already; analytics reads them rather than inventing a parallel sensor set.
Damper hunting at or near minimum often means a noisy flow signal, aggressive PID, a minimum below the controllable range, or duct static that is too high for stable low-flow control. Verify pickup tubing and calibration before retuning. A stuck or failed damper shows as command versus position mismatch, or airflow stuck high or low while the loop keeps writing. Airflow sensor drift, a bad K-factor, or a clogged pickup makes the controller look happy while a hood or traverse disagrees. Reheat fighting cooling shows as simultaneous heat and cool, a wrong mode or deadband, or a sensor lying about minimum flow so the box reheats while the AHU still cools hard.
When diagnosing a VAV box, co-trend airflow setpoint, measured flow, damper command (and position if separate), zone temperature, reheat command, and upstream duct static when the AHU exposes it. That set separates control hunting from sensor lies from plant-side static problems. FrostLogic Explore is Sensor Intelligence: it reads those BMS points and returns a prioritised queue. It is not a CMMS and not a dashboard replacement. Writes start off; predictive maintenance in Explore is the commercial path for VAV degradation ranked by cost and urgency.
Before you ask
A VAV system feeds conditioned air from a central air handling unit into zone VAV boxes. Each box meters airflow to match that zone's load. Space temperature resets an airflow setpoint between minimum and maximum; the box damper tracks the setpoint. At minimum flow, reheat often finishes the comfort job.
A VAV box is the zone terminal: a damper, usually an inlet flow sensor, a local controller, and often a reheat coil. It sits on the duct branch from the AHU and delivers the airflow the zone needs. It is not the air handling unit itself.
Pressure-independent means a flow loop holds delivered CFM (or l/s) using the inlet sensor and damper, even when duct static changes. The temperature loop only writes the airflow setpoint. Pressure-dependent boxes lack that flow hold and drift when upstream pressure moves.
Damper hunting near minimum, stuck or failed dampers, airflow sensor drift or bad K-factors, clogged pickups, and reheat fighting cooling. Hunting is often worse at low ΔP; check tubing and calibration before retuning PID.
Co-trend airflow setpoint, measured flow, damper command and position, zone temperature, reheat command, and upstream duct static when available. That set separates control, sensor and plant-side static problems without new hardware.
Explore reads the BMS points already on the VAV boxes and returns a prioritised queue of findings. It is Sensor Intelligence for predictive maintenance, not a CMMS and not a dashboard replacement. See predictive maintenance for buildings.
Related terms
From glossary to product
FrostLogic Explore is Sensor Intelligence: ranked findings from the BMS points already on your VAV boxes. Hunting, stuck dampers, sensor drift and reheat fights surface as a prioritised queue, not another alarm wall. Explore is not a CMMS.
See predictive maintenance in Explore